Abstract

The plumbing laboratory serves as practical learning facility design to simulate building water supply systems and support competency based-education in vocational institution. A reliable water distribution system is essential to ensure effective laboratory activities to provide hydraulic conditions that adequately represent actual building plumbing systems. This study aims to analyze the clean water distribution system of the plumbing laboratory by evaluating the design flow rate, hydraulic characteristic of the piping network, and the total dynamic head (TDH) required for pump selection. A descriptive quantitive approach was employed based on the existing laboratory conditions. Hydraulic analysis was conducted by estimating the design flow rate, hydraulic characteristic of the piping network, and the by estimating the design flow rate using the Plumbing Fixture Unit (PFU) method, calculating major head loss using the Hazen-Williams equation, and determining minor head loss based on the loss coefficients of pipe fittings. The result indicate that the total plumbing fixture unit of 31.5 corresponds to a design flow rate of 0.00132 m3/s. The hydraulic analysis yielded a major head loss of 6.23 m, a minor head loss of 29.50 m, and TDH of 38.03 m. Theses finding provide the hydraulic parameters required for selecting an appropiate pump to improve the laboratory water distribution system. The proposed approach can serve as a reference for developing plumbing laboratory facilities and enhancing practice-based learning in vocational education.

Keywords:

plumbing laboratory, clean water distribution system, head loss and pump.

References

[1] C. I. Asmarawati, S. A. Wibowo, and R. R. Gumilang, "Optimizing centrifugal water pump design for enhanced water use efficiency in Batam Marina Plantations," Journal Industrial Servicess, vol. 11, no. 1, 2025.

[2] M. Bilal, S. G. Sandi, B. M. Josey, and J. Gong, "A review of premise plumbing systems: From design and key performance domains to challenges and future research pathways for full-scale integration," Water Research, vol. 293, p. 125437, 2026.

[3] A. De Corte and K. Sörensen, "Optimisation of gravity-fed water distribution network design: A critical review," European Journal of Operational Research, vol. 228, no. 1, pp. 1–10, 2013

[4] M. S. M. Gani, A. N. Prabowo, and L. Apriyanti, "Planning of the clean water plumbing system for the West Java Provincial Environmental Agency Building," Jurnal Reka Lingkungan, vol. 2, no. 2, pp. 95–106, 2021.

[5] A. Gustiawan, Muchlisinalahuddin, and R. K. Arief, "Analysis of water flow rate requirements and determination of the type of pump used for the 13 Raya Permai Housing Complex," JTTM: Jurnal Terapan Teknik Mesin, vol. 3, no. 1, pp. 19–26, 2022.

[6] T. D. Hirrel, "System curves and pump selection," Journal - American Water Works Association, vol. 81, no. 7, pp. 67–73, 1989.

[7] M. E. Matlakala and D. V. Von Kallon, "Optimization of the pumping capacity of centrifugal pumps based on system analysis," MATEC Web of Conferences, vol. 347, p. 00024, 2021.

[8] M. E. Matlakala, D. V. V. Kallon, S. P. Simelane, and P. M. Mashinini, "Impact of design parameters on the performance of centrifugal pumps," Procedia Manufacturing, vol. 35, pp. 197–206, 2019.

[9] M. E. Matlakala, D. V. V. Kallon, K. F. Nkoana, B. D. Mafu, and S. B. Mkhwanazi, "Effect of suction diameter variations on performance of centrifugal pump," in Open Innovation (OI), pp. 170–173, 2019.

[10] A. Musnal and Fitrianti, "Synchronization of storage tank volume, disposal well volume and electric submersible pump (ESP) pump capacity in disposal well field A," Journal of Renewable Energy & Mechanics, vol. 4, no. 2, pp. 88–96, 2021.

[11] A. Rosytha, D. I. Yuliastuti, A. Nursandah, and M. Ismianto, "Analysis of the pumping capacity of Pulopancikan Pump House for Flood Control in Gresik Regency," Publikasi Riset Orientasi Teknik Sipil (PROTEKSI), vol. 7, no. 2, pp. 202–208, 2025.

[12] M. K. Singh and V. Kekatos, "On the Flow Problem in Water Distribution Networks: Uniqueness and Solvers," arXiv preprint arXiv:1901.03676, 2019.

[13] S. T. Sumaryanto, M. Solikin, and P. S. Pudyastuti, "Evaluation of Flood Pump Capacity in the Madiun City Area to Overcome Waterlogging in the Catchment Area of the City's Drainage Channel," Eduvest – Journal of Universal Studies, vol. 5, no. 9, pp. 11711–11728, 2025.

[14] G. Takács, "A critical comparison of TDH calculation models in manual ESP design procedures," Journal of Petroleum Science and Engineering, vol. 201, p. 108210, 2021.

[15] Y. Wang, K. T. Yok, W. Wu, A. R. Simpson, E. Weyer, and C. Manzie, "Minimizing pumping energy cost in real-time operations of water distribution systems using economic model predictive control," Journal of Water Resources Planning and Management, vol. 147, no. 7, p. 04021038, 2021.

[16] A. D. Wicaksono, S. Hadi, A. C. Wardhana, A. D. Arok, and A. J. K. Juach, "Centrifugal pump maintenance planning with a capacity of 650 liters/minute for 2026," Manufaktur: Publikasi Sub Rumpun Ilmu Keteknikan Industri, vol. 3, no. 4, pp. 13–20, 2025.

Author Biographies

Benedicta Dian Alfanda, Department of Marine Machinery Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Mahasin Maulana Achmad, Department of Marine Machinery Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Ekky Nur Budianto, Department of Marine Machinery Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Kiki Dwi Wulandari, Department of Shipbuilding Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Intan Rahmahwati, Department of Marine Machinery Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Muhammad Ali Reza, Department of Marine Machinery Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Vena Rizky, Department of Marine Machinery Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Ammar Galang Galang, Department of Marine Machinery Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Teguh Prasetyo, Department of Marine Machinery Engineering, Politeknik Perkapalan Negeri Surabaya, Jl. Teknik Kimia ITS, Sukolilo, Surabaya. Indonesia

Author Origin : Indonesia

Downloads

Download data is not yet available.

How to Cite

Alfanda, B. D., Achmad, M. M., Budianto, E. N., Wulandari, K. D., Rahmahwati, I., Reza, M. A., … Prasetyo, T. (2026). Hydraulic Analysis of Clean Water Distribution System in Plumbing Laboratory for Determining Pump Capacity. International Journal of Science and Environment (IJSE), 6(4), 605–612. https://doi.org/10.51601/ijse.v6i4.858

Similar Articles

<< < 6 7 8 9 10 11 12 13 14 15 > >> 

You may also start an advanced similarity search for this article.